Specifications / Shape dimension

Specifications

Fuel Kerosene、Light Oil、A.Oil
Standard Pressure Oil 50kPa
Air 6kPa
Atomizing Air 6 kPa
Accessories Regulating Cock
Type Capacity
kW (×1,000kcal/h)
Air Flow Rate(Nm3/h) Connection
Air Atomizing
Air
Air Atomizing
Air
Oil
LXO-1A 58(50) 60 2.5 Rc 1 1/2 Rc 1/2 Rc 3/8
LXO-2A 93(80) 96 3.5
LXO-3A 140(120) 144 6.5 Rc 2
LXO-4A 174(150) 180 6.5
LXO-5A 233(200) 240 10.0 Rc 2 1/2 Rc 3/4
LXO-6A 350(300) 360 10.0 Rc 3
LXO-7A 465(400) 480 18.0 Rc 4 Rc 1
LXO-8A 700(600) 720 18.0

※In placing an order for square tiles,affix “A” to the end of the model No.(Ex.LXO-1A)

Dimension



※ LXO-1 to 4 Site Hole Positions   ※ LXO-5 to 8 Site Hole Positions

Type A B C D E F G H J K L M N P Q
(G)
R
(G)
Mass
(kg)
LXO-1A 574 170 141 101 99 14 35 32 139 □150 94 175 205 15  3/4 1/2 25
LXO-2A
LXO-3A 144
LXO-4A
LXO-5A 708 198 197 138 112 55 179 □230 124 265 300  3/4 56
LXO-6A 181 134
LXO-7A 790 250 200 160 117 16 60 192 □280 174 320  350  1 85
LXO-8A

Download of DXF data

※ Download procedure

  1. Put the cursor on the model designation of the outline drawing you want to download, and click the right button of the mouse.
  2. Select “Save Target As (A)” on the menu.
  3. Select a location to save, and click “Save.”
    ※ Some security software does not permit downloading. If that happens, set the securities to “OFF” before downloading.

Flame Pattern

Condition
In the Air
Air Pressure 6kPa
Fuel Kerosene
Excess Air Ratio 1.0
Type ØD (mm) L (mm) L1 (mm)
LXO-1A 80 650 150
LXO-2A 100 750 150
LXO-3A 120 900 170
LXO-4A 120 900 170
LXO-5A 140 1,100 198
LXO-6A 180 1,300 198
LXO-7A 300 1,500 250
LXO-8A 400 1,800 250

MODEL TYPE SEARCH