SECTRON

[SEC] Sectron (Air-Fuel Control Unit)

Catalog
PRODUCT MANUAL
OPERATION MANUAL

Summary

This is an epoch-making air/gas ratio regulating equipment containing a micro-computer developed for burners used in industrial fields. Air temperature, air flow and gas flow are displayed at the front panel and also error message is displayed. This can be installed easily in existing furnaces and has the advantage of saving energy for industrial furnaces using city gas or other fuels.

Specifications / Shape dimension

Specifications

Item Specifications
Power AC100~240V 50/60Hz
Working Conditions (1)Temperature 0-45℃
(2)Temperature 0-45℃
(3)No condensation allowed
Display 4.3″ LCD touch panel
Power consumption Under 37VA
Dimensions and mass H105×W180×D182; 1.9kg

Download of DXF data

※ Download procedure

  1. Put the cursor on the model designation of the outline drawing you want to download, and click the right button of the mouse.
  2. Select “Save Target As (A)” on the menu.
  3. Select a location to save, and click “Save.”
    ※ Some security software does not permit downloading. If that happens, set the securities to “OFF” before downloading.

Fuel save ratio

This diagram shows the fuel save ratio when the air ratio is corrected and the combustion air is preheated at the same time (Excerption from the Industrial Furnace Energy Saving Handbook)

Confoguration of devices

Device name Type Quantity Remarks
Gas Sectron SEC-Ⅴ SEC-Ⅴ 1 Power AC100~240V Mass 1.9kg
Differential Pressure P-3000 2 0~3.0kPa
Temperature Sensor KL-200 1 Sheath Type K φ8×200L
Metering Orifice MO
(Each For Air And Gas)
2
Control Valve For Gas AZP,TZP 20~80 1
Control Motor CM-101T H/L ,ECM3000
Equivalent
1 Equipped With Limit Switch
Balance Regulator GIK GIK,SGX-NZT 1
Oil Sectron SEC-Ⅴ 1 Power AC100~240V Mass 1.9kg
Differential Pressure P-3000
P92M-30,P92M-29 ※
1 0~3.0kPa
Temperature Sensor KL-200 1 Sheath Type K φ8×200L
Oil Flow Sensor LSF40,41,45 1 50L/h,100L/h,500L/h
Metering Orifice MO(Each For Air) 1
Oil Filter FH150-02,04 1 20μm Rc1/4,Rc1/2
Oil Control Valve CR-10,15 1
Control Motor CM-101T H/L ,ECM3000
Equivalent
1 Equipped With Limit Switch
Oil Ratio Regulator FD-3 1

※Differential pressure transmitter P-3000 is a converter with a function of automatic zero-point adjustment for use in pressure measurement to convert air pressure to electric current. Depending on the ambient temperature, the zero point (output at pressure zero) may be deviated. However, owing to this automatic zero-point adjustment function, P-3000 requires no maintenance. Upon turning on the power supply, the automatic zero-point adjustment is performed 1 times in 20 minutes. Simplified types without this automatic zero-point adjustment function are also available as PU30.

Flow sheet

This is to regulate the combustion air flow through output signal from temperature controller of a furnace. Air flow is sensed as a delta pressure of a air flow meter installed in air lines and the signal of it is put into the micro computer of a Sectron. Calculating the input simultaneously, the Sectron moves fuel regulating valve and regulate fuel flow in proportion to air flow, in order to fire at fuel air ration set in advance.