Characteristics
Adjacent heating is possible because the flame is wide and short. This is a burner heating material centrally by radiation of the flame.
Specifications / Shape dimension
Specifications
Fuel | Kerosene、Light Oil |
Standard Pressure | Oil 50kPa Air 6kPa Atomizing Air 13 kPa |
Accessories | Regulating Cock |
Type | Capacity kW (×1,000kcal/h) |
Air Flow Rate(Nm3/h) | Connection | |||
Air | Atomizing Air |
Air | Atomizing Air |
Oil | ||
SFO-1F | 58(50) | 60 | 3.1 | Rc 1 1/2 | Rc 1/2 | Rc 3/8 |
SFO-2F | 116(100) | 120 | 5.4 | Rc 2 | ||
SFO-3F | 233(200) | 240 | 11.5 | Rc 2 1/2 | Rc 3/4 | |
SFO-4F | 350(300) | 360 | 16.0 | Rc 3 | ||
SFO-5F | 580(500) | 600 | 30.0 | 100A(JIS5K) |
Dimension
Type | A | B | C | D | E | F | G | H | J |
SFO-1F | 553 | 148 | 142 | 101 | 99 | 63 | 32 | 35 | 141 |
SFO-2F | 146 | ||||||||
SFO-3F | 693 | 205 | 175 | 138 | 112 | 55 | 180 | ||
SFO-4F | 182 | ||||||||
SFO-5F | 790 | 235 | 217 | 158 | 117 | 60 | 168 | ||
Type | K | L | M | N | P | Q(G) | Mass(kg) |
SFO-1F | 250 | 17 | 350 | 320 | 15 | 3/4 | 42 |
SFO-2F | |||||||
SFO-3F | 350 | 20 | 450 | 410 | 19 | 87 | |
SFO-4F | |||||||
SFO-5F | 400 | 500 | 460 | 1 | 129 |
Download of DXF data
※ Download procedure
- Put the cursor on the model designation of the outline drawing you want to download, and click the right button of the mouse.
- Select “Save Target As (A)” on the menu.
- Select a location to save, and click “Save.”
※ Some security software does not permit downloading. If that happens, set the securities to “OFF” before downloading.
Flame Pattern
Condition | |
In the Air | |
Air Pressure | 6kPa |
Fuel | Kerosene |
Excess Air Ratio | 1.1 |
Type | ØD (mm) | L (mm) | L1 (mm) |
SFO-1F | 180 | 150 | 160 |
SFO-2F | 200 | 200 | 160 |
SFO-3F | 350 | 350 | 220 |
SFO-4F | 450 | 400 | 220 |
SFO-5F | 550 | 500 | 250 |