Characteristics
Flow rates of gas and air can be gained only by operating the handle. The gas burner is widely applied for heating air.
Specifications / Shape dimension
Specifications
Fuel | Fuel Gases |
Standard Pressure | Gas 2~10kPa Air WF-3 0.5kPa WF-4,5 1kPa |
Flame Safeguard System | UV Phototube |
Type | Capacity kW (×1,000kcal/h) |
Air Flow Rate (Nm3/h) |
WF-3 | 47(40)81(70)116(100) | 51・90・129 |
WF-4 | 140(120)233(200)350(300) | 154・254・386 |
WF-5 | 465(400)640(550)814(700) | 514・707・900 |
Dimension
Type | A | B | C | D | E | F | G | H | J | K | L | M | N | Mass(kg) | |
WF-3 | 507 | 125 | 125 | 202 | 82 | 121 | 566 | 263 | 326 | 145 | 175 | 13 | 3/4 | 32 | |
WF-4 | 644 | 180 | 157 | 274 | 91 | 175 | 735 | 343 | 306 | 200 | 235 | 15 | 1 1/4 | 42 | |
WF-5 | 780 | 235 | 214 | 337 | 110 | 230 | 851 | 420 | 346 | 250 | 300 | 19 | 2 | 76 |
Download of DXF data
※ Download procedure
- Put the cursor on the model designation of the outline drawing you want to download, and click the right button of the mouse.
- Select “Save Target As (A)” on the menu.
- Select a location to save, and click “Save.”
※ Some security software does not permit downloading. If that happens, set the securities to “OFF” before downloading.
Flow sheet
Flame Pattern
Condition | |
In the Air | |
Air Pressure | 1kPa |
Fuel | LPG |
Excess Air Ratio | 1.1 |
Type | ØD (mm) | L (mm) | L1 (mm) |
WF-3-4 | 110 | 250 | 125 |
WF-3-7 | 120 | 350 | 125 |
WF-3-10 | 130 | 450 | 125 |
WF-4-12 | 160 | 500 | 180 |
WF-4-20 | 180 | 700 | 180 |
WF-4-30 | 200 | 900 | 180 |
WF-5-40 | 210 | 1,000 | 235 |
WF-5-55 | 230 | 1,200 | 235 |
WF-5-70 | 260 | 1,500 | 235 |
Technical data
1. Flame temperature distribution
Flame temperature distribution | |
Burner | WF-4-12 |
Capacity | 140kW |
Fuel | LPG |
Air Pressure | 1kPa |
Measure | PR thermocouple |
Type | Power |
WF-3-4 | 0.2kw 100V・200V |
WF-3-7 | |
WF-3-10 | |
WF-4-12 | 0.4kw 100V・200V |
WF-4-20 | |
WF-4-30 | |
WF-5-40 | 1.0kw 200V |
WF-5-55 | |
WF-5-70 | 1.5kw 200V |
2. Unit sample